3.15.8.3 Signals
Table 78: GOOSERCV_INT32 Output signals
Name Type Description
OUT INT32 Output signal
VALID BOOLEAN Output signal
3.16 Type conversion function blocks
3.16.1 QTY_GOOD function block
3.16.1.1 Function block
Figure 64: Function block
3.16.1.2 Functionality
The good signal quality function QTY_GOOD evaluates the quality bits of the input
signal and passes it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (logic function
output, binary input, application function output or received GOOSE signal). Due
to application logic quality bit propagation, each (simple and even combined) signal
has quality which can be evaluated.
The OUT output indicates quality good of the input signal. Input signals that have no
quality bits set or only test bit is set, will indicate quality good status.
3.16.1.3 Signals
Table 79: QTY_GOOD Input signals
Name Type Default Description
IN Any 0 Input signal
Table 80: QTY_GOOD Output signals
Name Type Description
OUT BOOLEAN Output signal