Parameter Values (Range) Unit Step Default Description
Str 3 delay shot 3 0...300000 ms 10 0 Delay time for
start3 3rd reclose
Str 3 delay shot 4 0...300000 ms 10 0 Delay time for
start3, 4th reclose
Str 4 delay shot 1 0...300000 ms 10 0 Delay time for
start4, 1st reclose
Str 4 delay shot 2 0...300000 ms 10 0 Delay time for
start4 2nd reclose
Str 4 delay shot 3 0...300000 ms 10 0 Delay time for
start4 3rd reclose
Str 4 delay shot 4 0...300000 ms 10 0 Delay time for
start4, 4th reclose
9.4.9 Monitored data
Table 1010: DARREC Monitored data
Name Type Values (Range) Unit Description
DISA_COUNT BOOLEAN
0=False
1=True
Signal for counter disa-
bling
FRQ_OPR_CNT INT32 0...2147483647 Frequent operation
counter
FRQ_OPR_AL BOOLEAN
0=False
1=True
Frequent operation
counter alarm
STATUS Enum
-1=Not defined
1=Ready
2=InProgress
3=Successful
4=WaitingForTrip
5=TripFromProtection
6=FaultDisappeared
7=WaitToComplete
8=CBclosed
9=CycleUnsuccessful
10=Unsuccessful
11=Aborted
AR status signal for
IEC61850
INPRO_1 BOOLEAN
0=False
1=True
Reclosing shot in pro-
gress, shot 1
INPRO_2 BOOLEAN
0=False
1=True
Reclosing shot in pro-
gress, shot 2
INPRO_3 BOOLEAN
0=False
1=True
Reclosing shot in pro-
gress, shot 3
INPRO_4 BOOLEAN
0=False
1=True
Reclosing shot in pro-
gress, shot 4
INPRO_5 BOOLEAN
0=False
1=True
Reclosing shot in pro-
gress, shot 5
DISCR_INPRO BOOLEAN
0=False
1=True
Signal indicating that
discrimination time is
in progress
Table continues on the next page
1MRS757644 H Control functions
620 series
Technical Manual
1043