Parameter Values (Range) Unit Step Default Description
Dsr time shot 1 0...10000 ms 100 0 Discrimination
time for first re-
closing
Dsr time shot 2 0...10000 ms 100 0 Discrimination
time for second re-
closing
Dsr time shot 3 0...10000 ms 100 0 Discrimination
time for third re-
closing
Dsr time shot 4 0...10000 ms 100 0 Discrimination
time for fourth re-
closing
Auto wait time 0...60000 ms 10 2000 Wait time for re-
closing condition
fullfilling
Auto lockout reset
0=False
1=True
1=True Automatic lockout
reset
Protection crd limit 1...5 1 1 Protection coordi-
nation shot limit
Protection crd
mode
1=No condition
2=AR inoperative
3=CB close manual
4=AR inop, CB man
5=Always
4=AR inop, CB man Protection coordi-
nation mode
Control line 0...63 1 63 Control line, de-
fines INIT inputs
which are protec-
tion signals
Enable shot jump
0=False
1=True
1=True Enable shot jump-
ing
CB closed Pos sta-
tus
0=False
1=True
0=False Circuit breaker
closed position sta-
tus
Blk signals CBB1 0...63 1 0 Blocking lines for
CBB1
Blk signals CBB2 0...63 1 0 Blocking lines for
CBB2
Blk signals CBB3 0...63 1 0 Blocking lines for
CBB3
Blk signals CBB4 0...63 1 0 Blocking lines for
CBB4
Blk signals CBB5 0...63 1 0 Blocking lines for
CBB5
Blk signals CBB6 0...63 1 0 Blocking lines for
CBB6
Blk signals CBB7 0...63 1 0 Blocking lines for
CBB7
Str 2 delay shot 1 0...300000 ms 10 0 Delay time for
start2, 1st reclose
Str 2 delay shot 2 0...300000 ms 10 0 Delay time for
start2 2nd reclose
Str 2 delay shot 3 0...300000 ms 10 0 Delay time for
start2 3rd reclose
Str 2 delay shot 4 0...300000 ms 10 0 Delay time for
start2, 4th reclose
Str 3 delay shot 1 0...300000 ms 10 0 Delay time for
start3, 1st reclose
Str 3 delay shot 2 0...300000 ms 10 0 Delay time for
start3 2nd reclose
Table continues on the next page
Control functions 1MRS757644 H
1042 620 series