Parameter Values (Range) Unit Step Default Description
Op number fault 1...10000 1 1000 Number of opera-
tions possible at
rated fault current
Inactive Alm days 0...9999 1 2000 Alarm limit value of
the inactive days
counter
Travel time Clc
mode
1=From Cmd to Pos
2=From Pos to Pos
2=From Pos to Pos Travel time calcu-
lation mode selec-
tion
Table 884: SSCBR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Opening time Cor -100...100 ms 1 10 Correction factor
for open travel time
in ms
Closing time Cor -100...100 ms 1 10 Correction factor
for CB close travel
time in ms
Counter initial Val 0...99999 1 0 The operation num-
bers counter initial-
ization value
Ini Acc currents Pwr 0.00...20000.00 0.01 0.00 Initial value for ac-
cumulation energy
(Iyt)
Life alarm level 0...99999 1 500 Alarm level for CB
remaining life
Pressure alarm
time
0...60000 ms 1 10 Time delay for gas
pressure alarm in
ms
Pres lockout time 0...60000 ms 10 10 Time delay for gas
pressure lockout in
ms
Ini inactive days 0...9999 1 0 Initial value of the
inactive days coun-
ter
Inactive Alm hours 0...23 h 1 0 Alarm time of the
inactive days coun-
ter in hours
7.1.8 Monitored data
Table 885: SSCBR Monitored data
Name Type Values (Range) Unit Description
T_TRV_OP FLOAT32 0...60000 ms Travel time of the CB
during opening opera-
tion
T_TRV_CL FLOAT32 0...60000 ms Travel time of the CB
during closing opera-
tion
T_SPR_CHR FLOAT32 0.00...99.99 s The charging time of
the CB spring
NO_OPR INT32 0...99999 Number of CB opera-
tion cycle
INA_DAYS INT32 0...9999 The number of days CB
has been inactive
CB_LIFE_A INT32 -99999...99999 CB Remaining life
phase A
CB_LIFE_B INT32 -99999...99999 CB Remaining life
phase B
Table continues on the next page
1MRS757644 H Condition monitoring functions
620 series