Table 204: UDFCNT Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Counter load value 0...2147483647 1 10000 Preset counter val-
ue
Reset counter
0=Cancel
1=Reset
0=Cancel Resets counter val-
ue
Load counter
0=Cancel
1=Load
0=Cancel Loads the counter
to preset value
3.17.15.7 Monitored data
Table 205: UDFCNT Monitored data
Name Type Values (Range) Unit Description
CNT_VAL INT64 0...2147483647 Output counter
value
3.18 Factory settings restoration
In case of configuration data loss or any other file system error that prevents the
protection relay from working properly, the whole file system can be restored to
the original factory state. All default settings and configuration files stored in the
factory are restored. For further information on restoring factory settings, see the
operation manual.
3.19 Load profile record LDPRLRC
3.19.1 Function block
Figure 114: Function block
3.19.2 Functionality
The protection relay is provided with a load profile recorder. The load profile feature
stores the historical load data captured at a periodical time interval (demand
interval). Up to 12 load quantities can be selected for recording and storing in a
1MRS757644 H
Basic functions
620 series
Technical Manual
207