3.14.4.4 Signals
Table 68: RESTVTR Input signals
Name Type Default Description
Uo INT32-UL0 0 IEC61850-9-2 residual
voltage
Table 69: RESTVTR Output signals
Name Type Description
ALARM BOOLEAN Alarm
WARNING BOOLEAN Warning
3.14.4.5 Settings
Table 70: RESTVTR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Primary voltage 0.100...440.000 kV 0.001 11.547 Primary voltage
Secondary voltage 60...210 V 1 100 Secondary voltage
Amplitude Corr 0.9000...1.1000 0.0001 1.0000 Amplitude correc-
tion
Angle correction -20.0000...20.0000 deg 0.0001 0.0000 Angle correction
factor
3.14.4.6 Monitored data
Monitored data is available in three locations.
Monitoring > I/O status > Analog inputs
Monitoring > IED status > SMV traffic
Monitoring > IED status > SMV accuracy
3.15 GOOSE function blocks
GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32 data
types.
Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by
bad data quality bits or GOOSE communication failure. See IEC 61850 engineering
guide for details.
1MRS757644 H
Basic functions
620 series
Technical Manual
139