ABB Relion 620 Series - Directional Three-Independent-Phase Directional Overcurrent Protection Dph3 Xpdoc

ABB Relion 620 Series
1224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Characteristic Value
Retardation time <35 ms
Operate time accuracy in
definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in in-
verse time mode
±5.0% of the theoretical value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
4.1.3.12 Technical revision history
Table 291: DPHHPDOC Technical revision history
Technical revision Change
B
Added a new input NON_DIR
C Step value changed from 0.05 to 0.01 for the
Time multiplier
setting.
D Monitored data VMEM_USED indicating volt-
age memory use.
E Internal improvement.
Table 292: DPHLPDOC Technical revision history
Technical revision Change
B
Added a new input NON_DIR
C Step value changed from 0.05 to 0.01 for the
Time multiplier
setting.
D Monitored data VMEM_USED indicating volt-
age memory use.
E Internal improvement.
4.1.4 Directional three-independent-phase directional
overcurrent protection DPH3xPDOC
4.1.4.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Directional three-independent-
phase directional overcurrent
protection, low stage
DPH3LPDOC
3_3I> -> 67-1_3
Directional three-independent-
phase directional overcurrent
protection, high stage
DPH3HPDOC 3I_3>> -> 67-2_3
3
Maximum
Start value
= 2.5 × I
n
,
Start value
multiples in range of 1.5...20
Protection functions 1MRS757644 H
298 620 series
Technical Manual