Table 828: UPCALH Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Operate pulse time 100...20000 ms 1 100 Operate pulse time
Signal pwr on delay 300...500 ms 1 300 Signal power on de-
lay time
Table 829: UPCALH Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
CB open hold delay 300...500 ms 1 300 CB open hold delay
time
5.8.8 Technical data
Table 830: UPCALH Technical data
Characteristic Value
Operate time accuracy ±1.0% of the set value or ±20 ms
1MRS757644 H Protection related functions
620 series
Technical Manual
865