Name Type Values (Range) Unit Description
CUTOUT_INPRO BOOLEAN
0=False
1=True
Signal indicating that
cut-out time is in pro-
gress
SUC_RECL BOOLEAN
0=False
1=True
Indicates a successful
reclosing sequence
UNSUC_CB BOOLEAN
0=False
1=True
Indicates an unsuccess-
ful CB closing
CNT_SHOT1 INT32 0...2147483647 Resetable operation
counter, shot 1
CNT_SHOT2 INT32 0...2147483647 Resetable operation
counter, shot 2
CNT_SHOT3 INT32 0...2147483647 Resetable operation
counter, shot 3
CNT_SHOT4 INT32 0...2147483647 Resetable operation
counter, shot 4
CNT_SHOT5 INT32 0...2147483647 Resetable operation
counter, shot 5
COUNTER INT32 0...2147483647 Resetable operation
counter, all shots
SHOT_PTR INT32 1...7 Shot pointer value
MAN_CB_CL BOOLEAN
0=False
1=True
Indicates CB manual
closing during reclosing
sequence
SOTF BOOLEAN
0=False
1=True
Switch-onto-fault
DARREC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
9.4.10 Technical data
Table 1011: DARREC Technical data
Characteristic Value
Operate time accuracy ±1.0 % of the set value or ±20 ms
9.4.11 Technical revision history
Table 1012: DARREC Technical revision history
Technical revision Change
B
The PROT_DISA output removed and re-
moved the related settings
C
The default value of the
CB closed Pos status
setting changed from "True" to "False"
D
SHOT_PTR output range 0...7 (earlier 0...6)
Table continues on the next page
Control functions 1MRS757644 H
1044 620 series
Technical Manual