6.2.7 Settings
Table 840: CCSPVC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation On / Off
Start value 0.05...0.20 xIn 0.01 0.05 Minimum operate
current differential
level
Table 841: CCSPVC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Max operate cur-
rent
1.00...5.00 xIn 0.01 1.50 Block of the func-
tion at high phase
current
6.2.8 Monitored data
Table 842: CCSPVC Monitored data
Name Type Values (Range) Unit Description
IDIFF FLOAT32 0.00...40.00 xIn Differential current
CCSPVC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
6.2.9 Technical data
Table 843: CCSPVC Technical data
Characteristic Value
Operate time
1
<30 ms
6.2.10 Technical revision history
Table 844: CCSPVC Technical revision history
Technical revision Change
B Internal improvement
C Internal improvement
D Internal improvement
1
Including the delay of the output contact
Supervision functions 1MRS757644 H
884 620 series
Technical Manual