14.2 Power supply
Table 1085: Power supply
Description Type 1 Type 2
U
aux
nominal 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 24, 30, 48, 60 V DC
48, 60, 110, 125, 220, 250 V DC
Maximum interruption time in the auxili-
ary DC voltage without resetting the re-
lay
50 ms at U
n
rated
U
aux
variation 38...110% of U
n
(38...264 V AC) 50...120% of U
n
(12...72 V DC)
80...120% of U
n
(38.4...300 V DC)
Start-up threshold 19.2 V DC (24 V DC × 80%)
Burden of auxiliary voltage supply under
quiescent (P
q
)/operating condition
DC <18.0 W (nominal
1
)/<22.5 W (max.
2
)
AC <19.0 W (nominal
1
)/<23.0 W (max.
2
)
DC <18.5 W (nominal
1
)/<22.5 W (max.
2
)
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Fuse type T4A/250 V
1
During the power consumption measurement, the relay is powered at rated auxiliary energizing
voltage and the energizing quantities are energized without any binary output being active
2
During the power consumption measurement, the relay is powered at rated auxiliary energizing
voltage and the energizing quantities are energized to activate at least half of the binary outputs
1MRS757644 H Technical data