3.16.2 QTY_BAD function block
3.16.2.1 Function block
Figure 65: Function block
3.16.2.2 Functionality
The bad signal quality function QTY_BAD evaluates the quality bits of the input
signal and passes it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (logic function
output, binary input, application function output or received GOOSE signal). Due
to application logic quality bit propagation, each (simple and even combined) signal
has quality which can be evaluated.
The OUT output indicates quality bad of the input signal. Input signals that have any
other than test bit set, will indicate quality bad status.
3.16.2.3 Signals
Table 81: QTY_BAD Input signals
Name Type Default Description
IN Any 0 Input signal
Table 82: QTY_BAD Output signals
Name Type Description
OUT BOOLEAN Output signal
3.16.3 QTY_GOOSE_COMM function block
3.16.3.1 Function block
Figure 66: Function block
Basic functions
1MRS757644 H
146 620 series
Technical Manual