3.1.5 Authorization settings
Table 10: Authorization settings
Parameter Values (Range) Unit Step Default Description
Local override
0=False
1
1=True
2
1=True Disable authority
Remote override
0=False
3
1=True
4
1=True Disable authority
Local viewer 0 Set password
Local operator 0 Set password
Local engineer 0 Set password
Local administrator 0 Set password
Remote viewer 0 Set password
Remote operator 0 Set password
Remote engineer 0 Set password
Remote adminis-
trator
0 Set password
Authority logging
1=None
2=Configuration
change
3=Setting group
4=Setting group,
control
5=Settings edit
6=All
4=Setting group,
control
Authority logging
level
1
Authorization override disabled, LHMI password required
2
Authorization override enabled, LHMI password not required
3
Authorization override disabled, communication tools request a password to enter the IED
4
Authorization override enabled, other communication tools than WHMI do not request a pass-
word to enter the IED
1MRS757644 H Basic functions
620 series
Technical Manual