EasyManua.ls Logo

ABB Relion 620 Series - Settings

ABB Relion 620 Series
1224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.1.6 Signals
Table 767: INRPHAR Input signals
Name Type Default Description
I_2H_A SIGNAL 0 Second harmonic
phase A current
I_1H_A SIGNAL 0 Fundamental fre-
quency phase A cur-
rent
I_2H_B SIGNAL 0 Second harmonic
phase B current
I_1H_B SIGNAL 0 Fundamental fre-
quency phase B cur-
rent
I_2H_C SIGNAL 0 Second harmonic
phase C current
I_1H_C SIGNAL 0 Fundamental fre-
quency phase C cur-
rent
BLOCK BOOLEAN 0=False Block input status
Table 768: INRPHAR Output signals
Name Type Description
BLK2H BOOLEAN Second harmonic based
block
5.1.7 Settings
Table 769: INRPHAR Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 5...100 % 1 20 Ratio of the 2.
to the 1. harmonic
leading to restraint
Operate delay time 20...60000 ms 1 20 Operate delay time
Table 770: INRPHAR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 771: INRPHAR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time