3.1.16 DNP3 settings
Table 22: DNP3 settings
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
5=off Operation Off / On
Port
1=COM 1
2=COM 2
3=Ethernet - TCP 1
4=Ethernet
TCP+UDP 1
3=Ethernet - TCP 1 Communication interface se-
lection
Unit address 1...65519 1 1 DNP unit address
Master address 1...65519 1 3 DNP master and UR address
Mapping select 1...2 1 1 Mapping select
ClientIP 0.0.0.0 IP address of client
TCP port 20000...65535 1 20000 TCP Port used on ethernet
communication
TCP write authority
0=No clients
1=Reg. clients
2=All clients
2=All clients 0=no client controls allowed;
1=Controls allowed by regis-
tered clients; 2=Controls al-
lowed by all clients
Link keep-alive 0...65535 s 1 0 Link keep-alive interval for
DNP
Validate master addr
1=Disable
2=Enable
1=Disable Validate master address on
receive
Self address
1=Disable
2=Enable
2=Enable Support self address query
function
Need time interval 0...65535 min 1 30 Period to set IIN need time bit
Time format
0=UTC
1=Local
1=Local UTC or local. Coordinate with
master.
CROB select timeout 1...65535 s 1 10 Control Relay Output Block
select timeout
Data link confirm
0=Never
1=Only Multiframe
2=Always
0=Never Data link confirm mode
Data link confirm TO 100...65535 ms 1 3000 Data link confirm timeout
Data link retries 0...65535 1 3 Data link retries count
Data link Rx to Tx delay 0...255 ms 1 0 Turnaround transmission de-
lay
Data link inter char delay 0...20 char 1 4 Inter character delay for in-
coming messages
App layer confirm
1=Disable
2=Enable
1=Disable Application layer confirm
mode
App confirm TO 100...65535 ms 1 5000 Application layer confirm and
UR timeout
App layer fragment 256...2048 bytes 1 2048 Application layer fragment
size
UR mode
1=Disable
2=Enable
1=Disable Unsolicited responses mode
Table continues on the next page