14.7 Signal output with high make and carry
Table 1091: Signal output with high make and carry
Description Value
1
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit
time constant L/R <40 ms
1 A/0.25 A/0.15 A
Minimum contact load 100 mA at 24 V AC/DC
1
X100: SO1
X105: SO1, SO2, when any of the protection relays is equipped with BIO0005.
X110: SO1, SO2 when REF620 or RET620 is equipped with BIO0005
X115: SO1, SO2 when REF620 or REM620 is equipped with BIO0005
Technical data 1MRS757644 H
1198 620 series
Technical Manual