Table 834: TCSSCBR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Operate delay time 20...300000 ms 1 3000 Operate delay time
Table 835: TCSSCBR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 20...60000 ms 1 1000 Reset delay time
6.1.8 Monitored data
Table 836: TCSSCBR Monitored data
Name Type Values (Range) Unit Description
TCSSCBR Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
6.1.9 Technical revision history
Table 837: TCSSBR Technical revision history
Technical revision Change
B Internal improvement
C Internal improvement
6.2 Current circuit supervision CCSPVC
6.2.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Current circuit supervision CCSPVC MCS 3I MCS 3I
Supervision functions 1MRS757644 H
876 620 series