ABB Relion 620 Series - Shunt Capacitor Bank Switching Resonance Protection, Current Based SRCPTOC794

ABB Relion 620 Series
1224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.12.2.9 Technical data
Table 758: CUBPTOC Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f
n
±2 Hz
1.5 % of the set value or 0.002 × I
n
Start time
1
,
2
Typically 26 ms
Reset time Typically 40 ms
Reset ratio Typically 0.96
Operate time accuracy in definite time mode 1 % of the theoretical value or ±20 ms
Operate time accuracy in inverse definite mini-
mum time mode
5 % of the theoretical value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n × f
n
, where n = 2,3,4,5,..
4.12.2.10 Technical revision history
Table 759: CUBPTOC Technical revision history
Technical revision Change
B Selection name for Recorded unbalance
changed.
4.12.3 Shunt capacitor bank switching resonance protection,
current based SRCPTOC
4.12.3.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Shunt capacitor bank switching
resonance protection, current
based
SRCPTOC TD> 55TD
4.12.3.2 Function block
Figure 415: Function block symbol
1
Fundamental frequency current = 1.0 × I
n
, current before fault = 0.0 × I
n
, fault current = 2.0 ×
Start
value
, results based on statistical distribution of 1000 measurements
2
Includes the delay of the signal output contact
Protection functions 1MRS757644 H
794 620 series
Technical Manual