Name Type Values (Range) Unit Description
I_NAT_ANGL FLOAT32 -179.00...179.00 deg Recorded natu-
ral unbalance
current angle
I_COM_AMPL FLOAT32 0.00...5.00 xIn Compensated
unbalance cur-
rent amplitude
I_COM_ANGL FLOAT32 -179.00...179.00 deg Compensated
unbalance cur-
rent angle
COUNT_BR1_A INT32 0...2147483647 Number of ele-
ment failures in
branch1 phase-A
COUNT_BR2_A INT32 0...2147483647 Number of ele-
ment failures in
branch2 phase-A
COUNT_BR1_B INT32 0...2147483647 Number of ele-
ment failures in
branch1 phase-B
COUNT_BR2_B INT32 0...2147483647 Number of ele-
ment failures in
branch2 phase-B
COUNT_BR1_C INT32 0...2147483647 Number of ele-
ment failures in
branch1 phase-C
COUNT_BR2_C INT32 0...2147483647 Number of ele-
ment failures in
branch2 phase-C
FAIL_COUNT INT32 0...2147483647 Total number of
element failures
CUBPTOC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
I-unb FLOAT32 0.00...5.00 xIn Measured neu-
tral unbalance
current ampli-
tude