EasyManua.ls Logo

ABB Relion 620 Series - Unbalance Protection; Negative-Sequence Overcurrent Protection NSPTOC

ABB Relion 620 Series
1224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Values (Range) Unit Description
ID_C FLOAT32 0.00...80.00 xln Differential current
phase C
MHZPDIF Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.3.6.11 Technical data
Table 538: MHZPDIF Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the current measured: f
n
±2
Hz
±1.5% of the set value or ±0.002 x I
n
Operate time , Minimum Typical Maximum
I
Fault
= 2.0 × set
Start Value
(one phase fault)
13 ms 17 ms 21 ms
I
Fault
= 2.0 × set
Start Value
(three phases fault)
11 ms 14 ms 17 ms
Reset time <40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value of ±20 ms
4.4 Unbalance protection
4.4.1 Negative-sequence overcurrent protection NSPTOC
4.4.1.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Negative-sequence overcurrent
protection
NSPTOC I2> 46
1
Measurement mode
= “Peak-to-Peak”, current before fault = 0.0 × I
n
, f
n
= 50 Hz, fault current with
nominal frequency injected from random phase angle, results based on statistical distribution of
1000 measurements.
2
Includes the delay of the signal output contact.
1MRS757644 H Protection functions
620 series
Technical Manual
609

Table of Contents

Other manuals for ABB Relion 620 Series

Related product manuals