start setting for HIxPDIF in the example is set as 0.8 pu HIxPDIF operates before
HZCCxSPVC.
6.4.7 Signals
Table 850: HZCCASPVC Input signals
Name Type Default Description
I_A SIGNAL 0 Phase A current
BLOCK BOOLEAN 0=False Block signal for activating blocking
mode
Table 851: HZCCBSPVC Input signals
Name Type Default Description
I_B SIGNAL 0 Phase B current
BLOCK BOOLEAN 0=False Block signal for activating blocking
mode
Table 852: HZCCCSPVC Input signals
Name Type Default Description
I_C SIGNAL 0 Phase C current
BLOCK BOOLEAN 0=False Block signal for activating blocking
mode
Table 853: HZCCASPVC Output signals
Name Type Description
ALARM BOOLEAN Alarm output
Table 854: HZCCBSPVC Output signals
Name Type Description
ALARM BOOLEAN Alarm output
Table 855: HZCCCSPVC Output signals
Name
Type Description
ALARM BOOLEAN Alarm output
6.4.8 Settings
1MRS757644 H
Supervision functions
620 series
Technical Manual