EasyManua.ls Logo

ABB Relion 620 Series - Master Trip TRPPTRC; Identification; Function Block; Functionality

ABB Relion 620 Series
1224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.3 Master trip TRPPTRC
5.3.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Master trip TRPPTRC Master Trip 94/86
5.3.2 Function block
Figure 428: Function block
5.3.3 Functionality
The master trip function TRPPTRC is used as a trip command collector and handler
after the protection functions. The features of this function influence the trip signal
behavior of the circuit breaker. The minimum trip pulse length can be set when the
non-latched mode is selected. It is also possible to select the latched or lockout
mode for the trip signal.
5.3.4 Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
When the TRPPTRC function is disabled, all trip outputs intended to go
through the function to the circuit breaker trip coil are blocked.
The operation of TRPPTRC can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
Figure 429: Functional module diagram
Protection related functions
1MRS757644 H
816 620 series
Technical Manual

Table of Contents

Other manuals for ABB Relion 620 Series

Related product manuals