Parameter Values (Range) Unit Step Default Description
Init signals CBB1 0...63 1 0 Initiation lines for
CBB1
Init signals CBB2 0...63 1 0 Initiation lines for
CBB2
Init signals CBB3 0...63 1 0 Initiation lines for
CBB3
Init signals CBB4 0...63 1 0 Initiation lines for
CBB4
Init signals CBB5 0...63 1 0 Initiation lines for
CBB5
Init signals CBB6 0...63 1 0 Initiation lines for
CBB6
Init signals CBB7 0...63 1 0 Initiation lines for
CBB7
Shot number CBB1 0...5 1 0 Shot number for
CBB1
Shot number CBB2 0...5 1 0 Shot number for
CBB2
Shot number CBB3 0...5 1 0 Shot number for
CBB3
Shot number CBB4 0...5 1 0 Shot number for
CBB4
Shot number CBB5 0...5 1 0 Shot number for
CBB5
Shot number CBB6 0...5 1 0 Shot number for
CBB6
Shot number CBB7 0...5 1 0 Shot number for
CBB7
Frq Op counter lim-
it
0...250 1 0 Frequent operation
counter lockout
limit
Frq Op counter
time
1...250 min 1 1 Frequent operation
counter time
Frq Op recovery
time
1...250 min 1 1 Frequent operation
counter recovery
time
Auto init 0...63 1 0 Defines INIT lines
that are activated
at auto initiation
Table 1009: DARREC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Manual close mode
0=False
1=True
0=False Manual close mode
Wait close time 50...10000 ms 50 250 Allowed CB closing
time after reclose
command
Max wait time 100...1800000 ms 100 10000 Maximum wait
time for
BLK_RECL_T re-
lease
Max trip time 100...10000 ms 100 10000 Maximum wait
time for deactiva-
tion of protection
signals
Max Thm block
time
100...1800000 ms 100 10000 Maximum wait
time for thermal
blocking signal de-
activation
Cut-out time 0...1800000 ms 100 10000 Cutout time for
protection coordi-
nation
Table continues on the next page