EasyManua.ls Logo

ABB Relion 620 Series - Page 121

ABB Relion 620 Series
1224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.13.2.3 Input linear scaling
Each RTD/mA input can be scaled linearly by the construction of a linear output
function in respect to the input. The curve consists of two points, where the y-axis
(
Input minimum
and
Input maximum
) defines the input range and the x-axis (
Value
minimum
and
Value maximum
) is the range of the scaled value of the input.
The input scaling can be bypassed by selecting
Value unit
= "Ohm" when
Input mode
= "Resistance" is used and by selecting
Value unit
= "Ampere"
when
Input mode
= "0...20 mA" is used.
Example for linear scaling
Milliampere input is used as tap changer position information. The sensor
information is from 4 mA to 20 mA that is equivalent to the tap changer
position from -36 to 36, respectively.
Input maximum
Input minimum
Input mode
”0..20mA”
4 mA
20 mA
Value minimum
-36
AI_VAL#
Value maximum
36
Value unit
”Dimensionless”
X130-Input#
Figure 44: Milliampere input scaled to tap changer position information
3.13.2.4 Measurement chain supervision
Each input contains a functionality to monitor the input measurement chain. The
circuitry monitors the RTD channels continuously and reports a circuitry break
of any enabled input channel. If the measured input value is outside the limits,
minimum/maximum value is shown in the corresponding output. The quality of the
corresponding output is set accordingly to indicate misbehavior in the RTD/mA
input.
Table 53: Function identification, limits for the RTD/mA inputs
Input Limit value
RTD temperature, high > 200 °C
RTD temperature, low < -40 °C
mA current, high > 23 mA
Resistance, high > 2000 Ω
1MRS757644 H Basic functions
620 series
Technical Manual
121

Table of Contents

Other manuals for ABB Relion 620 Series

Related product manuals