Table 149: TPSGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Pulse time 0...300 s 1 0 Minimum pulse time
Technical revision history
Table 150: TPSGAPC Technical revision history
Technical revision Change
B Outputs now visible in menu
C Internal improvement
3.17.2.3 Minimum pulse timer TPMGAPC
Function block
Figure 90: Function block
Functionality
The Minimum minute pulse timer function TPMGAPC contains two independent
timers. The function has a settable pulse length (in minutes). The timers are used
for setting the minimum pulse length for example, the signal outputs. Once the
input is activated, the output is set for a specific duration using the
Pulse time
setting. Both timers use the same setting parameter.
Figure 91: A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is longer
than Pulse time setting
Signals
Table 151: TPMGAPC Input signals
Name Type Default Description
IN1 BOOLEAN 0=False Input 1
IN2 BOOLEAN 0=False Input 2