Figure 135: Operating zones at minimum magnitude levels
Level detector
The measured phase currents are compared phasewise to the set
Start value
. If the
measured value exceeds the set
Start value
, the level detector reports the exceeding
of the value to the phase selection logic. If the ENA_MULT input is active, the
Start
value
setting is multiplied by the
Start value Mult
setting.
The protection relay does not accept the
Start value
or
Start value Mult
setting if the product of these settings exceeds the
Start value
setting
range.
The start value multiplication is normally done when the inrush detection function
(INRPHAR) is connected to the ENA_MULT input.