4.2.3.7 Settings
Table 429: INTRPTEF Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward Directional mode
Operate delay time 40...1200000 ms 10 500 Operate delay time
Voltage start value 0.05...0.50 xUn 0.01 0.20 Voltage start value
Table 430: INTRPTEF Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Operation mode
1=Intermittent EF
2=Transient EF
1=Intermittent EF Operation criteria
Uo signal Sel
1=Measured Uo
2=Calculated Uo
1=Measured Uo Selection for used
Uo signal
Table 431: INTRPTEF Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 40...60000 ms 1 500 Reset delay time
Peak counter limit 2...20 1 2 Min requirement
for peak counter
before start in IEF
mode
Min operate cur-
rent
0.01...1.00 xIn 0.01 0.01 Minimum operating
current for transi-
ent detector
4.2.3.8 Monitored data
Table 432: INTRPTEF Monitored data
Name
Type Values (Range) Unit Description
FAULT_DIR Enum
0=unknown
1=forward
2=backward
3=both
Detected fault direction
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
INTRPTEF Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS757644 H Protection functions
620 series
Technical Manual
427