Table 472: MFADPSDE Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Operation mode
1=Intermittent EF
3=General EF
4=Alarming EF
3=General EF Operation criteria
Table 473: MFADPSDE Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io Selection for used
Io signal
Uo signal Sel
1=Measured Uo
2=Calculated Uo
1=Measured Uo Selection for used
Uo signal
Peak counter limit 2...20 1 2 Peak counter limit
for restriking EF
Start delay time 30...60000 ms 1 30 Start delay time
Reset delay time 0...60000 ms 1 500 Reset delay time
Pol reversal
0=False
1=True
0=False Rotate polarizing
quantity
4.2.8.8 Monitored data
Table 474: MFADPSDE Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
FAULT_DIR Enum
0=unknown
1=forward
2=backward
3=both
Detected fault
direction
DIRECTION Enum
0=unknown
1=forward
2=backward
3=both
Direction infor-
mation
Table continues on the next page
Protection functions 1MRS757644 H
500 620 series
Technical Manual