EasyManua.ls Logo

ABB Relion 620 Series - Page 538

ABB Relion 620 Series
1224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 483: TR2PTDF settings corresponding to the power transformer vector
groups and zero-sequence elimination
Vector group of
the transformer
Winding 1 type Winding 2 type Clock number Zro A
Elimination
Yy0 Y y Clk Num 0 Not needed
YNy0 YN y Clk Num 0 HV side
YNyn0 YN yn Clk Num 0 HV & LV side
Yyn0 Y yn Clk Num 0 LV side
Yy2 Y y Clk Num 2 Not needed
YNy2 YN y Clk Num 2 Not needed
YNyn2 YN yn Clk Num 2 Not needed
Yyn2 Y yn Clk Num 2 Not needed
Yy4 Y y Clk Num 4 Not needed
YNy4 YN y Clk Num 4 Not needed
YNyn4 YN yn Clk Num 4 Not needed
Yyn4 Y yn Clk Num 4 Not needed
Yy6 Y y Clk Num 6 Not needed
YNy6 YN y Clk Num 6 HV side
YNyn6 YN yn Clk Num 6 HV & LV side
Yyn6 Y yn Clk Num 6 LV side
Yy8 Y y Clk Num 8 Not needed
YNy8 YN y Clk Num 8 Not needed
YNyn8 YN yn Clk Num 8 Not needed
Yyn8 Y yn Clk Num 8 Not needed
Yy10 Y y Clk Num 10 Not needed
YNy10 YN y Clk Num 10 Not needed
YNyn10 YN yn Clk Num 10 Not needed
Yyn10 Y yn Clk Num 10 Not needed
Yd1 Y d Clk Num 1 Not needed
YNd1 YN d Clk Num 1 Not needed
Yd5 Y d Clk Num 5 Not needed
YNd5 YN d Clk Num 5 Not needed
Yd7 Y d Clk Num 7 Not needed
YNd7 YN d Clk Num 7 Not needed
Yd11 Y d Clk Num 11 Not needed
YNd11 YN d Clk Num 11 Not needed
Dd0 D d Clk Num 0 Not needed
Dd2 D d Clk Num 2 Not needed
Dd4 D d Clk Num 4 Not needed
Table continues on the next page
Protection functions 1MRS757644 H
538 620 series
Technical Manual

Table of Contents

Other manuals for ABB Relion 620 Series

Related product manuals