Vector group of
the transformer
Winding 1 type Winding 2 type Clock number Zro A
Elimination
Yy10 Y y Clk Num 10 Not needed
YNy10 YN y Clk Num 10 Not needed
YNyn10 YN yn Clk Num 10 Not needed
Yyn10 Y yn Clk Num 10 Not needed
Yd1 Y d Clk Num 1 Not needed
YNd1 YN d Clk Num 1 Not needed
Yd5 Y d Clk Num 5 Not needed
YNd5 YN d Clk Num 5 Not needed
Yd7 Y d Clk Num 7 Not needed
YNd7 YN d Clk Num 7 Not needed
Yd11 Y d Clk Num 11 Not needed
YNd11 YN d Clk Num 11 Not needed
Dd0 D d Clk Num 0 Not needed
Dd2 D d Clk Num 2 Not needed
Dd4 D d Clk Num 4 Not needed
Dd6 D d Clk Num 6 Not needed
Dd8 D d Clk Num 8 Not needed
Dd10 D d Clk Num 10 Not needed
Dy1 D y Clk Num 1 Not needed
Dyn1 D yn Clk Num 1 Not needed
Dy5 D y Clk Num 5 Not needed
Dyn5 D yn Clk Num 5 Not needed
Dy7 D y Clk Num 7 Not needed
Dyn7 D yn Clk Num 7 Not needed
Dy11 D y Clk Num 11 Not needed
Dyn11 D yn Clk Num 11 Not needed
Yz1 Y z Clk Num 1 Not needed
YNz1 YN z Clk Num 1 Not needed
YNzn1 YN zn Clk Num 1 LV side
Yzn1 Y zn Clk Num 1 Not needed
Yz5 Y z Clk Num 5 Not needed
YNz5 YN z Clk Num 5 Not needed
YNzn5 YN zn Clk Num 5 LV side
Yzn5 Y zn Clk Num 5 Not needed
Yz7 Y z Clk Num 7 Not needed
YNz7 YN z Clk Num 7 Not needed
YNzn7 YN zn Clk Num 7 LV side
Table continues on the next page
Protection functions 1MRS757644 H
542 620 series
Technical Manual

Table of Contents

Other manuals for ABB Relion 620 Series

Related product manuals