Table 630: PSPTUV Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.5.7.7 Settings
Table 631: PSPTUV Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.010...1.200 xUn 0.001 0.500 Start value
Operate delay time 40...120000 ms 10 40 Operate delay time
Table 632: PSPTUV Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Voltage block value 0.01...1.00 xUn 0.01 0.20 Internal blocking
level
Enable block value
0=False
1=True
1=True Enable Internal
Blocking
Table 633: PSPTUV Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 634: PSPTUV Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Relative hysteresis 1.0...5.0 % 0.1 4.0 Relative hysteresis
for operation
4.5.7.8 Monitored data
Table 635: PSPTUV Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
PSPTUV Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS757644 H Protection functions
620 series
Technical Manual