Fault indication Fault
code
Additional
information
Fast self-
recovery
attempt
(# of
attempts)
Slow 10
min self-
recovery
(# of
attempts)
Immediate
permanen
t IRF-
mode
Action in permanent fault state
Internal Fault
Conf. error,X105
60 Start up error: Card
in slot X105 is
wrong type, is miss-
ing, does not be-
long to original con-
figuration or card
firmware is faulty.
No No Yes Check that the card in slot X105 is prop-
er type and properly installed. Check
that the plug-in unit is properly installed
and plug-in unit handle is properly fixed
to closed position. Then restart the re-
lay. If does not recover by restarting, it
is hardware module failure most likely.
Exchange the hardware module in slot
X105.
Internal Fault
Conf. error,X115
61 Start up error: Card
in slot X115 is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No No Yes Check that the card in slot X115 is prop-
er type and properly installed. Check
that the plug-in unit is properly installed
and plug-in unit handle is properly fixed
to closed position. Then restart the re-
lay.If does not recover by restarting, it
is hardware module failure most likely.
Exchange the hardware module in slot
X115.
Internal Fault
Conf. error,X000
62 Start up error: Card
in slot X000 is
wrong type, is miss-
ing, does not be-
long to original con-
figuration or card
firmware is faulty.
No No Yes "Check that the communication card in
slot X000 is proper type and properly
installed. Check that the plug-in unit is
properly installed and plug-in unit han-
dle is properly fixed to closed position.
Then restart the relay. If does not re-
cover by restarting, it is hardware mod-
ule failure most likely. Exchange the
communication module in slot X000. In
some rare cases also communication
storm may cause this. Detach the ether-
net communication cable(s) from the
communication module and reboot the
relay. If not recover,exchange the com-
munication module in slot X000. "
Internal Fault
Conf. error,X100
63 Start up error: Card
in slot X100 is
wrong type, is miss-
ing, does not be-
long to original con-
figuration or card
firmware is faulty.
No No Yes Check that the card in slot X100 is prop-
er type and properly installed. Check
that the plug-in unit is properly installed
and plug-in unit handle is properly fixed
to closed position. Then restart the re-
lay. If does not recover by restarting, it
is hardware module failure most likely.
Exchange the hardware module in slot
X100.
Internal Fault
Conf. error,X110
64 Start up error: Card
in slot X110 is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No No Yes Check that the card in slot X110 is prop-
er type and properly installed. Check
that the plug-in unit is properly installed
and plug-in unit handle is properly fixed
to closed position. Then restart the re-
lay. If does not then recover by restart-
ing, hardware module failure most likely.
Exchange the hardware module in slot
X110.
Internal Fault
Conf. error,X120
65 Start up error: Card
in slot X120 is
wrong type, is miss-
ing, does not be-
long to original con-
figuration or card
firmware is faulty.
No No Yes Check that the card in slot X120 is prop-
er type and properly installed. Check
that the plug-in unit is properly installed
and plug-in unit handle is properly fixed
to closed position. Then restart the re-
lay. If does not recover by restarting, it
is hardware module failure most likely.
Exchange the hardware module in slot
X120.
Table continues on the next page
Basic functions 1MRS757644 H
72 620 series
Technical Manual