Table 695: DUPPDPR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation On/Off
Table 696: DUPPDPR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Measurement
mode
1=PhsA, PhsB, PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
3=Pos Seq Selection of power
calculation method
Reset delay time 0...60000 ms 10 20 Reset delay time
Pol reversal
0=False
1=True
0=False Reverse the defini-
tion of the power
direction
Disable time 0...60000 ms 1000 0 Additional wait
time after CB clos-
ing
4.8.1.8 Monitored data
Table 697: DUPPDPR Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
P FLOAT32 -160.000...160.000 xSn Active power
Q FLOAT32 -160.000...160.000 xSn Reactive power
S FLOAT32 0.000...160.000 xSn Apparent power
PF_ANGLE FLOAT32 -180.00...180.00 deg Power factor angle
DUPPDPR Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Protection functions 1MRS757644 H
734 620 series
Technical Manual