Table 699: Power calculation
Measurement mode setting Power calculation
PhsA, PhsB, PhsC
S U I U I U I
a a b b c c
= ⋅ + + + ⋅
* * *
Arone
S U I U I
ab a bc c
= ⋅ − ⋅
* *
Pos Seq
PhsAB
S U I I
ab a b
= ⋅ ⋅ −
( )
3
* *
PhsBC
S U I I
bc b c
= ⋅ ⋅ −
( )
3
* *
PhsCA
S U I I
ca c a
= ⋅ ⋅ −
( )
3
* *
PhsA
PhsB
PhsC
If all three phase voltages and phase currents are fed to the protection
relay, the positive-sequence alternative is recommended.
The calculated powers S, P, Q and the power factor angle PF_ANGL are available in
the Monitored data view.
1MRS757644 H