Name Type Default Description
SYNC_OK BOOLEAN 1=True Synchronism-check OK
SYNC_ITL_BYP BOOLEAN 0=False Discards ENA_OPEN and
ENA_CLOSE interlocking when
TRUE
Table 963: DCXSWI Input signals
Name Type Default Description
POSOPEN BOOLEAN 0=False Apparatus open position
POSCLOSE BOOLEAN 0=False Apparatus close position
ENA_OPEN BOOLEAN 1=True Enables opening
ENA_CLOSE BOOLEAN 1=True Enables closing
BLK_OPEN BOOLEAN 0=False Blocks opening
BLK_CLOSE BOOLEAN 0=False Blocks closing
AU_OPEN BOOLEAN 0=False Executes the command for open di-
rection
1
,
2
AU_CLOSE BOOLEAN 0=False Executes the command for close di-
rection
1
,
2
ITL_BYPASS BOOLEAN 0=False Discards ENA_OPEN and
ENA_CLOSE interlocking when
TRUE
Table 964: ESXSWI Input signals
Name Type Default Description
POSOPEN BOOLEAN 0=False Apparatus open position
POSCLOSE BOOLEAN 0=False Apparatus close position
ENA_OPEN BOOLEAN 1=True Enables opening
ENA_CLOSE BOOLEAN 1=True Enables closing
BLK_OPEN BOOLEAN 0=False Blocks opening
BLK_CLOSE BOOLEAN 0=False Blocks closing
AU_OPEN BOOLEAN 0=False Executes the command for open di-
rection
1
,
2
AU_CLOSE BOOLEAN 0=False Executes the command for close di-
rection
1
,
2
ITL_BYPASS BOOLEAN 0=False Discards ENA_OPEN and
ENA_CLOSE interlocking when
TRUE
Table 965: CBXCBR Output signals
Name Type Description
SELECTED BOOLEAN Object selected
EXE_OP BOOLEAN Executes the command for open di-
rection
Table continues on the next page
1MRS757644 H Control functions
620 series
Technical Manual
989