Figure 19: PCM600: Communication protocol selection wizard
5. Select the port and insert the IP address of the physical IED to configure, see
Figure 20.
IEC09000713-2-en.vsd
IEC09000713 V2 EN-US
Figure 20: PCM600: Communication port and IP address
6. Cross-check that the IED whose IP address has been inserted, has been
detected online by PCM600, see Figure 16.
The user cannot scan data from the IED or proceed further if
the IED is not online or if the IP address is not correct.
7. Click the Scan option to scan/read the IED Type and IED Version for the IED
that is online, see Figure 21.
1MRK 511 398-UEN C Section 4
Setting up a project
670 series 2.2 IEC 51
Engineering manual