EasyManuals Logo

Allen-Bradley MicroLogix 1400 User Manual

Allen-Bradley MicroLogix 1400
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #356 background imageLoading...
Page #356 background image
342 Rockwell Automation Publication 1766-UM001I-EN-P - June 2015
Appendix F MicroLogix 1400 Distributed Network Protocol (DNP3)
70 2 File-Control -
authentication
29 (authenticate
file)
5B (free format) 129 (response) 5B (free format)
70 3 File Control - file
command
25 (open file) 5B (free format)
70 3 File Control - file
command
27 (delete file) 5B (free format)
70 4 File Control - file
command status
26 (close file) 5B (free format) 129 (response) 5B (free format)
70 5 File Control - file transport 1 (read file) 5B (free format)
70 5 File Control - file transport
2 (write file) 5B (free format)
70 6 File Control - file transport
status
129 (response) 5B (free format)
70 7 File-Control - file
descriptor
129 (response) 5B (free format)
80 1 Internal Indications -
Packed format
1 (read file) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
2 (write file) 00 (start-stop)
index=7
90 1 Application - Identifier 16 (init. appl.)
17 (start appl.)
18 (stop appl.)
5B (free format)
06 (no range, or all)
101 1 Binary Coded Decimal
Integers - small
1 (read file) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
130 (unsol. resp) 17, 28 (index)
101 2 Binary Coded Decimal
Integers - medium
No Object (function code only) 13 (cold restart)
No Object (function code only) 23 (delay meas.)
Implementation Table for Series A controllers
DNP Object Group & Variation Request
DNP3 Master may issue
MicroLogix 1400 must parse
Response
DNP3 Master must parse
MicroLogix 1400 may issue
Group
Num
Var Num Description Function Codes
(dec)
Qualifier Codes
(hex)
Function Codes
(dec)
Qualifier Codes
(hex)
Implementation Table for Series B controllers
DNP Object Group & Variation Request
DNP3 Master may issue
MicroLogix 1400 must parse
Response
DNP3 Master must parse
MicroLogix 1400 may issue
Group
Num
Var Num Description Function Codes
(dec)
Qualifier Codes (hex) Function Codes
(dec)
Qualifier Codes
(hex)
0211-239
241-243
248-250
252
Device Attribute
1 (read) 00, 01 (start-stop)
06 (no range, or all)
129 (response) 00 (start-stop)
0240
245-247
Device Attribute
1 (read) 00, 01 (start-stop)
06 (no range, or all)
129 (response) 00 (start-stop)
2 (write) 00, 01 (start-stop)
0 254 Device Attribute - Non-specific
all attributes request
1 (read) 00, 01 (start-stop)
06 (no range, or all)

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1400 and is the answer not in the manual?

Allen-Bradley MicroLogix 1400 Specifications

General IconGeneral
Processor32-bit
Expansion ModulesUp to 7 expansion I/O modules
Power Supply24V DC or 120/240V AC
Programming SoftwareRSLogix 500
Communication PortsEthernet, RS-232/RS-485 combo port
Controller TypeProgrammable Logic Controller (PLC)
SeriesMicroLogix
Digital Outputs12
Analog Inputs6 (embedded)
Analog Outputs2 (embedded)
High-Speed Counter6 high-speed counters
Pulse Output2 (embedded)
Ethernet PortYes

Related product manuals