EasyManuals Logo

Allen-Bradley PowerFlex 40 User Manual

Allen-Bradley PowerFlex 40
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #182 background imageLoading...
Page #182 background image
182 Publication IASIMP-QS001C-EN-P - October 2009
Chapter 13 Create a PowerFlex 40 Application
EtherNet/IP, ControlNet, and DeviceNet
Use the reference on page 181 to make the following parameter value edits on your
PowerFlex 40.
1. If your PowerFlex 40 has been previously used, reset it to factory defaults.
a. Change the value of parameter P041 from 0 to 1.
The drive is reset and fault F048 is displayed and blinks.
b. Press to clear the fault.
c. Press to return to editing parameters.
2. Change the value of parameters P036 and P038 from 0 to 5.
Changing these parameters switch control the Start Source and the Speed Reference
from the keypad to the communication port, giving you the ability to control these
functions from the RSLogix 5000 tags.
3. Press to accept parameter edits.
For EtherNet and ControlNet networks, go to Test the PowerFlex 40 Tags on page 183.
For a DeviceNet network, go to Test the PowerFlex 40 Tags
on page 185.

Table of Contents

Other manuals for Allen-Bradley PowerFlex 40

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 40 and is the answer not in the manual?

Allen-Bradley PowerFlex 40 Specifications

General IconGeneral
Output Voltage0 to Input Voltage
EnclosureIP20
Control MethodV/Hz, Sensorless Vector Control
CommunicationRS485
Frequency0 to 400 Hz
ProtectionOverload, Overvoltage, Undervoltage, Short Circuit
Operating Temperature-10 to 50°C (14 to 122°F)
Storage Temperature-40...70 °C (-40...158 °F)
Humidity5% to 95% non-condensing
Input Voltage200-240V AC, 380-480V AC, 500-600V AC (depending on model)