EasyManua.ls Logo

Ametek UPLC-II - Page 49

Ametek UPLC-II
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
January 2016 Page 3–3
Chapter 3. Applications
3
gle-phase voltage output proportional to the posi-
tive, negative, and zero sequence current input.
Sensitivity to different types of faults depends on
the weighting factors or constants designed into
the sequence current network. Adjustments to the
network are provided.
A squaring amplifier in the controlling relay con-
verts the single-phase voltage output to a square
wave. The positive voltage portion corresponds to
the positive half-cycle of the filter voltage wave
and the zero portion corresponds to the negative
half-cycle. The square wave is used to key the
UPLC-II™, transmitting to the remote terminal.
The square wave from the remote terminal is com-
pared to the local square wave, which has been
delayed by an amount equal to the absolute chan-
nel delay time. This comparison of the local and
remote square waves at each terminal determines
whether a fault is internal or external.
Fault detectors are used to determine whether a
fault has occurred and to supervise tripping. The
fault detectors must be overreaching, i.e., set sen-
sitively enough to operate for all internal phase
and ground faults.
Because overcurrent fault detectors are normally
used, voltage transformers are not required. Such
a scheme is current only. Fault detectors should be
set above maximum load, yet operate for all inter-
nal faults. Distance fault detectors, which require
voltage transformers, are used on heavy-loaded or
long lines when distance supervision is required.
3.1.2.1 Single Phase-Comparison
Blocking, Current Only
In the current only system, the UPLC-II™ is used
with two overcurrent fault detectors (FD
l and
FD2). FD1, the carrier start unit, is set more sensi-
Table 3–1. Directional Comparison Blocking Operations for External and Internal Faults
* For external faults, the CS unit or timer x/o assure that a blocking signal is established.
OPERATION FOR EXTERNAL AND INTERNAL FAULTS
Type of Fault Events at Station G Events at Station H
External (F
E
)
For external faults, the
CS unit or timer x/o
assure that a blocking
signal is established.
P
1
operates; S
1
does not see
fault. Blocking signal received
from station H. RR back con-
tacts open (or 1 signal negates
AND).
No trip.
S
2
operates to key transmitter.
Blocking signal sent to station
G. P
2
does not see fault.
No trip.
Internal (F
I
) P
1
operates; S
1
may or may
not operate, but P
1
operation
prevents transmission of a
blocking signal.
Breaker 1 tripped.
P
2
operates, S
2
may or may
not operate but P
2
operation
prevents transmission of a
blocking signal.
Breaker 2 tripped.

Table of Contents