Page 3–20   
UPLC-II™ System Manual
the receiver’s trip positive output. The
other wave, which has positive output
during  the  negative  half-cycle  of  the
sequence  current  network,  is  com-
pared to the receiver’s trip neg. output
in a second comparison circuit. 
On  internal  faults,  the  positive  half-
cycle of the local square wave lines up
with  the  received  trip  positive  output
to  provide  an AND-1  output.  On  the
negative  half-cycle,  this  local  square
wave  lines  up  with  the  received  trip
negative output to provide an AND-2
output. If an arming signal is received
(FD
2
and/or 21P) and either AND-1 or
AND-2 output exists for 4ms, an input
to  the  trip  flip  flop  initiates  breaker
tripping. The same operation occurs at
both terminals, tripping breakers 1 and
2  simultaneously  on  either  half-cycle
of fault current.
For tripping, both the trip positive and
trip  negative  frequencies  must  be
transmitted  through  the  internal  fault
via  Power-Line  Carrier  channels.  If
these frequencies are not received, the
receiver detects a loss of channel and
clamps  both  outputs  to  a  continuous
positive  state.  This  loss  of  channel
clamp enables  both  comparison  cir-
cuits,  allowing  the  system  to  trip  on
the local square wave input only. After
150ms,  the  system  output  clamps
these  to  the  zero  state.  At  this  point,
the  system  cannot  trip  and  is  locked
out. An  alarm  indicates  loss  of  chan-
nel. 
For external faults, the reversal of cur-
rent at one end shifts the square waves
essentially 180°. As a result, neither AND-1 nor AND-2 has the sustained output required to operate the
4ms timer. No trip occurs at either line terminal. 
Figure 3–11. Basic Operation of the Dual 
Phase Comparison Pilot Relaying System