Host Application Objects 201 (258)
Command Details: Indicate_Device
Category
Extended
Details
Command Code 1Eh
Valid for: Object Instance
Description
This command is optional. The module issues this command to inform the application that the DCP command
Set Control/Signal has been received on the network. This is used by engineering tools to identify the node
on the network. The application should flash its dedicated Network Status LED for 3 seconds after receiving
this command.
• Command Details
Field Contents Comments
CmdExt[0] (reserved)
CmdExt[1]
• Response Details
(no data)
Anybus
®