Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway 107
December 2003
Figure 25: Typical media gateway ground location
Grounding to an AC load center more than 50 feet (15.2 meters)
from media gateway
1 Mount the single-point ground block to any surface between the media gateways and the AC load
center single-point ground. The single-point ground block must be mounted to a non-metallic
surface.
2 At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
2
) media gateway
GROUND wire to the media gateway ground block. See Figure 26, Typical media gateway
grounding wiring diagram, on page 108.
3 Route the opposite end of the wire to the single-point ground block and connect.
4 At the next media gateway, connect a 6 AWG (#40) (16 4 mm
2
) media gateway GROUND wire to
the media gateway ground block.
NOTE:
If a media gateway is located remotely (in a separate room or building), route the media
gateway GROUND wire to an approved protective ground.
Figure notes
1 Media Gateway
2 Media Gateway Ground Terminal
Block
3 6 AWG (#40) (16 mm
2
) Media
Gateway GROUND Wire
4 AC Load Center
5 Less than 50 Wire feet (15.2 m)
6 Approved Ground
widmgrn2 KLC 091603
3
5
1
2
4
6