108 Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
5 Repeat connecting each media gateway to the single-point ground block.
6 Connect a 6 AWG (#40) (16 mm
2
) ground wire to an unused terminal on the single-point ground
block.
7 Route the ground wire to the AC load center ground and connect.
Figure 26: Typical media gateway grounding wiring diagram
Figure notes
1 Media Gateway
2 Media Gateway Ground Terminal
Block
3 6 AWG (#40) (16 mm
2
) Media
Gateway GROUND Wire
4 Single-Point Ground Block
5 6 AWG (#40) (16 4 mm
2
) Ground Wire to
Approved Ground
6 AC Load Center Single-Point Ground
7 Approved Ground
8 Over 50 ft. (15.2 m)
6
1 3
5
widfspg2 KLC 091603
8
4
2
7