Maintenance T1689 Technical Manual Rev 07
Preventative Maintenance MV3000 Air Cooled DELTA
Page 140
8.3 PREVENTATIVE MAINTENANCE
There are several preventive maintenance routines which should be performed to ensure optimum operating
efficiency of the system is maintained. GE Power Conversion recommends that these are performed bi-
annually, but individual applications may require a different maintenance schedule.
NOTE: All supplies must be isolated before preventative maintenance tasks are performed.
8.3.1 Bi-Annual Maintenance Routine
The following checks should be carried out every six months:
a) Ensure that all ventilation louvres to the cubicle are unobstructed;
b) Ensure the airflow through the cooling ducts is unobstructed.
c) Examine all power terminations for any signs of overheating;
d) Check that all electrical connections are secure. Torque settings are given in Appendix C: Recommended
Torque Settings;
e) Remove any accumulated dust from the system, using a vacuum cleaner with a non-conducting nozzle.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Avid Technology MV3000 DELTA and is the answer not in the manual?

Avid Technology MV3000 DELTA Specifications

General IconGeneral
BrandAvid Technology
ModelMV3000 DELTA
CategoryControl Unit
LanguageEnglish

Related product manuals