T1689 Technical Manual Rev 07 Specification
MV3000 Air Cooled DELTA Reactors, Inductors & Transformers
Page 65
2.13.5 Interbridge Transformer For DFE Drives
When using DELTA rectifier modules in a 12-pulse DFE drive, it is mandatory that an interbridge transformer
replaces the d.c. link inductor. In addition to performing the same functions as a d.c. link inductor, the
interbridge transformer forces sharing between the two rectifier bridges (one supply phase-shifted by 30°).
These naturally ventilated transformers are used with 12 pulse input rectifier systems - see Table 2-14.
Number
Overload)
Overload)
Supply
Voltage (V)
reactor
(m
)
Table 2–33. – Interbridge Transformers – Weight & Resistance
2.13.6 Losses
Power loss = Idc² x R
reactor
x 0.325 Watts
Where R
reactor
is in ohms
Idc is in amperes.