T1689 Technical Manual Rev 07 Specification
MV3000 Air Cooled DELTA Reactors, Inductors & Transformers
Page 63
2.13.2.3 Interface
The airflow path is the same as DELTA modules.
Cross-rail fixing positions are the same as DELTA modules.
Phase connections are made by busbar or cable between the rectifier module and reactor.
The module earth connection is made via M10 stud connection.
2.13.2.4 External Requirements
This module must be used with the DELTA Cooling System to obtain the full current rating.
The reactor requires an additional 250mm (9.84”) of cross rail to attach to the standard DELTA
cross rails this may increase overall cubicle width.
An external 230V a.c. supply is required to power the DELTA Cooling System.
An additional set of air inlet / outlet ducts are required to properly channel the cooling path using
these modules.
NOTE: These reactors will not fit into a 600mm deep cubicle without modification.
2.13.3 D.C. Link Inductor for DFE Drives
This inductor is used in conjunction with the DFE input reactor, to provide a more continuous current into the
machine bridge and reduce the harmonics that the drive imposes on the supply. This item is mandatory when
using three-phase, 6 pulse, rectifier modules.
NOTE: When using twelve pulse rectifier modules the use of an Interbridge transformer replaces the mandatory
requirement for the d.c. link inductor.
Figure 2–24. DC Link Inductor
These naturally ventilated inductors are used with 6 pulse input rectifiers - see Table 2–32.