© AXION TECHNOLOGIES LTD. TROUBLESHOOTING
5.2.8. GENERAL ERROR MESSAGES
FLASHING ''JUNCTION BOX RELAY DEFECTIVE" ON LCD
INDICATES A DEFECTIVE RELAY ON JUNCTION BOARD OR DEFECTIVE CONTROL
CONSOLE
CHECK PASSES FAILS/CORRECTIVE ACTION
STEP 1
Front Sign Junction board
GO TO STEP
2
Replace Junction board
STEP 2
If Control Console functionality
matches that of Table "Console does
not turn on" in Section 5.1.2
GO TO STEP
3
Replace Control Console
STEP 3
Wiring between Control Console and
Junction board
Replace Control Console power
cable
FLASHING ''CONSOLE CONFIG. CORRUPT'' (SYSTEM NOT PRESENT) ON LCD
CHECK PASSES FAILS/CORRECTIVE ACTION
STEP 1
Press "ENTER" and follow instructions
on LCD
GO TO STEP
2
STEP 2
The Control Console reconfigures.
This should solve the problem
Replace Control Console
''CONFIG DIFFERS FROM ACTIVE DATABASE"
INDICATES THAT DATABASE CONFIGURATION DIFFERS FROM THAT OF THE
CONTROL CONSOLE NETWORK
CHECK PASSES FAILS/CORRECTIVE ACTION
STEP 1
Press "ENTER". Control Console
operates normally
GO TO STEP
2
STEP 2
Go to Menu 13 to find out which sign
has a database problem (See Section
4.1.1.9)
GO TO STEP
3
STEP 3
Download database corresponding to
sign network configuration or
reconfigure Control Console
User Manual (Revision A) Document No.: 3042145 Page 54