Baumer_EAx_EtherNetIP_EN_MNL 53/81 www.baumer.com
02.20
Total
Measurement
Range (TMR)
Maximum value violated
0x03 (Invalid Parameter
Value)
7
Total
Measurement
Range (TMR)
Parameter "TMR" > ("steps
per revolution” * “physical
multiturn range”)
0x03 (Invalid Parameter
Value)
8
Gear Factor
Mode
Maximum value violated
0x03 (Invalid Parameter
Value)
18
Gear Factor
Numerator
Minimum value violated
0x03 (Invalid Parameter
Value)
20
Gear Factor
Numerator
Maximum value violated
0x03 (Invalid Parameter
Value)
21
Gear Factor
Denominator
Minimum value violated
0x03 (Invalid Parameter
Value)
24
Gear Factor
Denominator
Maximum value violated
0x03 (Invalid Parameter
Value)
25
Gear Factor
Numerator
Gear Factor
Denominator
((TMR * Gear Factor
Denominator) / Gear
Factor Numerator) > 2^(32-
[“physical multiturn length”])
0x03 (Invalid Parameter
Value)
26
Velocity Unit
Maximum value violated
0x03 (Invalid Parameter
Value)
10
Velocity
Resolution
Steps
Parameter invalid
0x03 (Invalid Parameter
Value)
12
Velocity
Resolution
Turns
Parameter invalid
0x03 (Invalid Parameter
Value)
13
Velocity Update
Period
Minimum range violated
0x03 (Invalid Parameter
Value)
16
Velocity Filter
Depth
Minimum value violated
0x03 (Invalid Parameter
Value)
17
Set Preset
Request Value
Maximum value violated (>=
TMR)
0x03 (Invalid Parameter
Value)
28
Set Preset 32Bit
Maximum value violated (>=
TMR)
-
255 (general fault
code)
Instance (107) - Empty Configuration
The device supports an empty configuration assembly which is used for each connection.
Remark:
The empty configuration assembly is needed to check that no parameters are changed at a second IO
connection.