EasyManua.ls Logo

Baumer EA Series - Parameterization Behaviour

Default Icon
81 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Baumer_EAx_EtherNetIP_EN_MNL 41/81 www.baumer.com
02.20
7.6.15. Parameterization behaviour
The following chapter applies for all parameters of the Position Sensor Object marked with a “(c)” (see
Instance Attributes).
Parameterization via Configuration Assembly
A parameterization during start up is possible via the configuration assembly (see Instance (105) -
Configuration). All parameters of the assembly are immediately applied and stored during connection
establishment.
Parameterization via Acyclic Services
Depending on Attribute 110 (see Instance Attribute 110 - Set Parameter Non-Volatile) the acyclic encoder
parameterization changes. Both parameter behaviours are described the next chapters.
Default Parameter Behaviour
If attribute 110 has the value 0 (factory setting) the following parameter behaviour is valid:
The encoder works with the “Active Parameters”. The transitions can be executed by the according services
described in Position Sensor Object (0x23).
Transition
Service
Set
Set_Attribute_Single (see Instance Services)
Get
Get_Attribute_Single (see Instance Services)
Apply
Apply_Attributes (see Class Services)
Reset
Reset (see Class Services)
Save
Save (see Class Services)
Restore
Restore (see Class Services)
Alternative Parameter Behaviour
If attribute 110 is set to 1 the alternative parameter behaviour is applied. Parameters become active and are
stored immediately at the time when they are set. The following transitions (services) are no longer
accessible:
Apply
Save
Restore
The parameterization has to be done as described in Parameterization sequence.

Table of Contents

Related product manuals