7.14.4. Instance Attributes
Attr ID
Access
Rule
NV
Name
Data
Type
Description
of Attribute
Value
1
Get
V
Network
Topology
USINT
Current
network
topology
mode
0 indicates “Linear”
1 indicates “Ring”
2
Get
V
Network Status
USINT
Current
status of
network
0 indicates “Normal”
1 indicates “Ring Fault”
2 indicates “Unexpected
Loop Detected”
3 indicates “Partial Network
Fault”
4 indicates “Rapid
Fault/Restore Cycle”
10
Get
NV
Active
Supervisor
Address
STRUCT
of:
IP and/or
MAC
address of
the active
ring
supervisor
UDINT
Supervisor
IP Address
A Value of 0 indicates no IP
Address has been
configured for the device
ARRAY of
6 USINTs
Supervisor
MAC
Address
Ethernet MAC address
12
Get
NV
Capability
Flags
DWORD
Describes
the DLR
capabilities
of the
device
Bit 0: 0
Bit 1: 1
Bit 2-4: 0
Bit 5: 0
Bit 6: 0
Bit 7: 1
Bit 8-31: 0